Chapter III. Performance of Ventilation Systems
(Hood, etc.,
of Local Exhaust Ventilation Systems)
Article 14. The hood of a local exhaust ventilation system
(the ones stipulated by Chapter II; the same for this Chapter and item (2)
of Article 19-2) shall comply with the following provisions.
(1) Each hood shall be installed for
each emission source of organic solvent vapour.
(2) Hoods of outside mounting type shall
be installed as close as possible to the emission source of organic solvent
vapour.
(3) Mode of Function: The hood shall
be of a type and size suitable to suck in the vapour of the said organic solvents
in connection with the work methods, the status of vapour emission, specific
gravity of the vapour and the like.
2. An employer shall make ducts of the local
exhaust ventilation system as short as possible and minimize bending.
(Draft, etc.)
Article 15. When an air cleaner is mounted on a local
exhaust ventilation system, an employer shall install an exhaust fan at the
location where cleaned air flows. Whereas, this provision is not applied when
sucked vapour of organic solvents does not have a risk of explosion and does
not corrode the fan.
2. The employer shall install an air blower
or exhaust fan of a general ventilation system (opening of a duct when the
duct is used for the system) as close as possible to the emission source of
organic solvent vapour in a general ventilation system (those which are provided
for in Chapter II; the same for this Chapter and item (2) of Article 19-2).
(Exhaust Outlet)
Article 15-2. The employer shall keep the exhaust outlet of
local exhaust ventilation systems, push-pull type ventilation systems (here
refers to push-pull type ventilation systems installed conforming to the
provisions of Chapter II and same applies in this Chapter and Article 19-2
and item (6) of paragraph 1 of Article 33), general ventilation systems
and exhaust pipes, etc., specified in sub-paragraph 1 of Article 12, directly
open to the atmosphere.
2. The employer shall keep the exhaust outlet
of local exhaust ventilation systems, a push-pull type ventilation systems
(restricted to those installed in indoor workshops) or the exhaust pipes,
etc., specified in sub-paragraph 1 of Article 12, at a height of 1.5 m or
more from the roof. However, this shall not apply where the concentration
of the organic solvent discharged from the said outlet is lower than the concentration
specified by the Minister of Labour.
(Performance
of Local Exhaust Ventilation Systems)
Article 16. The local exhaust ventilation system shall
have a capacity to generate the controlled air velocity specified in the right
column of the following table corresponding to the types specified in the
left column of the same table.
Type
|
Controlled air velocity
(m/sec.)
|
Surrounding type hood
|
0.4
|
Outside
mounting hood
|
Lateral direction sucking type
|
0.5
|
Downward sucking type
|
0.5
|
Upward sucking type
|
1.0
|
Remarks 1) Controlled air velocity in this table
shall be defined as the one when all the hoods on the local exhaust ventilation
system are set open.
-
2) Controlled air velocity in this table shall be defined as
the air velocity specified below corresponding to the types of the hood:
-
(a) In the case of the surrounding type hood, the minimum air
velocity at the hood opening.
(b) In the case of the outside mounting type hood, the air velocity
at the most distant operation point from the hood opening within the range
of a hood which is to suck the vapour of organic solvents in the said area.
2. Notwithstanding the provision of the preceding
paragraph, when the local exhaust ventilation system falls under any one of
the following categories, such a local exhaust ventilation system shall have
a ventilating capacity of generating the controlled air velocity large enough
to provide air flow rates equivalent to those of the general ventilation system
which vary depending on the classification of the vapor-emitting organic solvents
as are designated respectively in Article 17.
(1) The local exhaust ventilation systems
are provided conforming to the provision of paragraph 1 of Article 6.
(2) The local exhaust ventilation systems
are installed in the place where the installation of general ventilation system
results in the exemption of the installation of the hermetically sealed container
of the organic solvent vapor source or the local exhaust ventilation system
because of the provision of paragraph 2 of Article 8, paragraph 1 of Article
9 or Article 11.
(Performance,
etc., of Push-Pull Type Ventilation System)
Article 16-2. The push-pull type ventilation system
shall have the construction and exert the performance designated by the Minister
of Labour.
(Performance
of General Ventilation Systems)
Article 17. A general ventilation system shall have the
capacity for per minute ventilation volumes as computed based on the equations
specified in the right column of the following table corresponding to the
classification specified in the left column of the same table (when organic
solvents of the different classifications are consumed simultaneously, the
per minute ventilation volumes computed separately by respective classifications
shall be added up).
Classification of organic solvents, etc.
|
Ventilation volume per minute
|
First-class organic solvents, etc.
|
Q = 0.3 W |
Second-class organic solvents, etc.
|
Q = 0.04 W
|
Third-class organic solvents, etc.
|
Q = 0.01 W
|
- Remarks:Q and W in this table stand for the following figures:
-
Q: Ventilation volume
per minute (unit: m3)
W: Weight of organic solvents
to be consumed in one working hour (unit: g)
2. The weight of organic solvents to be consumed
in one working hour stipulated in the preceding paragraph shall be as provided
for in the following items:
(1) Work specified in a) and b) of item
(6), paragraph 1 of Article 1: Weight of organic solvents evaporated in one
working hour.
(2) Work specified in c) throughf),
h), i) or k) of item (6), paragraph 1 of Article 1: Weight obtained by multiplying
a figure separately provided by the Minister of Labour by the weight of organic
solvents to be consumed in one working hour.
(3) Work specified in g) or j) of item
(6), paragraph1 of Article 1: Weight obtained by multiplying a figure separately
provided by the Minister of Labour by the weight of organic solvents applied
to or sticking to the materials to be dried or adhered, respectively, in one
working hour.
3. The provisions of the latter part of paragraph
2 of Article 2 shall be applied to the weight of organic solvents to be consumed
in one working hour of the work stipulated in the preceding paragraph.
(Operation of
Ventilation Systems)
Article 18. Where a local exhaust ventilation system
is installed, the employer shall operate said local exhaust ventilation system
in accordance with the models specified in the left column of the table in
paragraph 1 of Article 16 at a controlled air velocity equal to or above the
controlled air velocity specified respectively in the right column of the
same table when workers are engaged in organic solvents work.
2.
Notwithstanding the provision of the preceding paragraph, where the said local
exhaust ventilation system is covered by any of the provisions of items in
paragraph 2 of Article 16, it may be operated at a controlled air velocity
equal to or above the controlled air velocity stipulated in the same paragraph >.
3. Where
a push-pull type ventilation system is installed, the employer shall operate
the said push-pull type ventilation system so as to satisfy the conditions
stipulated by the Minister of Labour when workers are engaged in organic solvents
work.
4.
Where a general ventilation system is installed, the employer shall operate
the said general ventilation system in accordance with the classifications
stipulated in the left column of the table in paragraph 1 of the preceding
Article at a ventilation volume equal to or above the ventilation volume per
minute stipulated respectively in the right column of the same table when
workers are engaged in organic solvents work.
5. Where a local exhaust system, a push-pull type
ventilation system or a general ventilation system is installed, the employer
shall take the necessary measures to operate the said system effectively such
as installing a baffle to prevent air currents that impede ventilation.
(Special Measures for Local Exhaust Ventilation Systems)
Article
18-2. Notwithstanding the provision of paragraph 1 of the preceding Article,
where measurements of a workplace relating to the said local exhaust ventilation
system under the provision of paragraph 2 of Article 28 and the provision
of paragraph 5 of Article 65 of the Industrial Safety and Health
Law (called the "Law" below) and an evaluation of the said measurements
have been carried out during the said previous eighteen months and where
the results of the said evaluation are consistently classified in the first-grade
section, the employer may, after taking the following measures, operate
the said local exhaust ventilation system at a controlled air velocity
less than that stipulated in the right column of the table in paragraph
1 of Article 16 for the models described in the left column of the same
table when taking measurements of organic solvent concentration in order
to obtain the permission specified in paragraph 1 of the following Article.
1) Appoint a person
to check the following matters from among those with necessary competence
to check the said matters and have them check the said matters in advance.
a) That the controlled
air velocity is stable when the said local exhaust ventilation system is operated
at the relevant controlled air velocity
b) That the hood
of the said local exhaust ventilation system which is to extract organic solvent
vapour is able to extract organic solvent vapour from the most distant operation
point from the hood opening within the range of the said hood when the said
local exhaust ventilation system is operated at the relevant controlled air
velocity.
2) Workers engaged
in organic solvents work in the area of the said local exhaust ventilation
system shall be required to use air-supplied respirators or masks to prevent
organic solvent poisoning.
2. When requiring workers to use the air-supplied respirators stipulated
under the provision of sub-paragraph 2 of the preceding paragraph, the employer
shall take measures to ensure that the said workers do not inhale toxic air.
Article 18-3.
Notwithstanding the provision of paragraph 1 of Article 18, where a local
exhaust ventilation system is operated at a controlled air velocity less
than that specified in the right column of the table in paragraph 1 of
Article 16 for each of the model types specified in the left column of
the same table under the provisions of the preceding Article and measurements
are taken of organic solvent concentration (applies only to those carried
out in normal workplace conditions under the provision of paragraph 2 of
Article 65 of the Law and the provision of Article 3 of the Enforcement
Order for the style='background:yellow;'>Work Environment Measurement
Law (Ministry of Labour Ordinance No. 20 of 1975), the same applies in
the following paragraph) in the workplace related to the said local exhaust
ventilation system with the results evaluated in accordance with the provision
of paragraph 1 of Article 28-2 producing a first-grade section, the said
local exhaust ventilation system may be operated at the said controlled
air velocity (called "Exceptional Controlled Air Velocity" below)
with the permission of the Chief of the competent Labour Standards Inspection
Office.
2. An employer intending to obtain the permission covered in the
preceding paragraph shall attach the following documents concerning the application
for the local exhaust ventilation system to the Local Exhaust System Exceptional
Operation Permit Application Form (Form 2-2) and submit it to the Chief of
the competent Labour Standards Inspection Office.
1) A sketch of the
workplace
2) A written record of the results of measurements taken in
the said workplace during the eighteen months prior to the application under
the provisions of paragraph 2 of Article 28 and paragraph 5 of Article 65
of the Law and the evaluation of the said results of measurements under the
provision of paragraph 1 of Article 18-2
3) A written record
of the results of measurements of the concentration of organic solvents in
the said workplace with the said local exhaust ventilation system operated
at the exceptional controlled air velocity and the evaluation of the results
of measurement carried out in accordance with the provision of paragraph 1
of Article 28-2.
4) A written record
showing that the notification stipulated under the provision of the main text
of paragraph 1 of Article 88 of the Law (including cases where paragraph 2
of the same Article applies) has been carried out
5) A written record
of the results of voluntary inspections stipulated in paragraph 2 of Article
20 carried out during the two years prior to the application
3. When receiving a submission of an application provided for in
the provisions of the preceding paragraph, the Chief of the competent Labour
Standards Inspection Office shall notify in writing the said employer without
delay when he/she has decided to grant or not grant the permit under paragraph
1.
4. An employer in receipt of a permit under paragraph 1 shall
notify the Chief of the competent Labour Standards Inspection Office in writing
without delay of the matters under each item of paragraph 3 of Article 28
and the matters under each item of paragraph 2 of Article 28-2 when measurements
of the workplace to which the permit relates are carried out under the provision
of paragraph 2 of Article 28 and evaluation of the results of the said measurements
made under the provision of paragraph 1 of Article 28-2.
5. An employer in receipt of a permit under paragraph 1 shall inform
the Chief of the competent Labour Standards Inspection Office in writing without
delay when there are any changes to the details recorded on the application
form and documents under paragraph 2.
6. Where the evaluation in paragraph 4 was not in the first-grade
section and when it is deemed likely that the evaluation of the results of
the measurements of a workplace relating to a permit under paragraph 1 carried
out under paragraph 2 of Article 28 will not maintain the first-grade section
under paragraph 1 of Article 28-2, the Chief of the competent Labour Standards
Inspection Office shall cancel the said permit without delay.
|